Concrete operating rooms take months, cannot be expanded, and hide every cable behind a wall you have to break to service. YANING's modular glass wall operating room system replaces that with a prefabricated enclosure assembled from flush glazed panels, achieving ISO 7 (Class 10000) cleanliness in days rather than months, with full visual transparency for clinical supervision.
| Parameter | Value | Test Method |
|---|---|---|
| Cleanliness | ISO 7 (Class 10000), ISO 6 on request | ISO 14644-1 particle count |
| Room pressure | +15 to +25 Pa positive, -10 to -25 Pa negative | Calibrated differential gauge |
| Air change rate | 25-40 ACH | Balometer at supply diffusers |
| Airborne recovery | Under 15 minutes to ISO 7 | ISO 14644-3 recovery test |
| Leakage | Under 0.5% of room volume per hour | Pressure decay test |
| Airtightness of glazing | No measurable infiltration at 30 Pa | Smoke pencil walk test |
Hospital refurbishment inside a live building is the strongest case: panels arrive flat packed, pass through a standard 900mm lift door, and are assembled in a corridor without demolition dust. The same system serves ophthalmic suites, hybrid catheterisation labs, dental surgical rooms and veterinary operating theatres, and it can be dismantled and reconfigured when a department is redesigned.
Because the enclosure is bolted rather than welded, a two-room suite can become a four-room suite by adding panel bays at a weekend, with no wet trades and no fire watch permits. Two hospitals in Southeast Asia have already used this to convert a single theatre into a three-theatre block while keeping one room operational throughout.
Every panel bay can be released with a single tool, so a failed gas outlet or a jammed door closer is repaired from the corridor side without dismantling glazing or shutting the theatre. Spare gaskets, panel clips and a door roller set ship with each project as a standard commissioning kit.
Tell us your room dimensions and required cleanliness class and we will return a glass wall layout with door swing, service void routing and a panel-by-panel installation sequence.