YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom

Product Details

Place of Origin: China

Brand Name: YANING

Certification: CE ISO

Model Number: YN-FFU-E02

Payment & Shipping Terms

Minimum Order Quantity: 1pcs

Price: USD+139~129+1PCS

Packaging Details: Standard Export Packing

Delivery Time: 5-8 work days

Payment Terms: T/T

Supply Ability: 1+PCS+7Day

Get Best Price
Highlight:

Customized Size Fan Filter Unit

,

380V 50Hz Ffu Fan Filter Unit

,

Adjustable Levels Fan Filter Unit

Material:
Cold Rolled Steel/ Stainless Steel/ Galvalume
HEPA Filter:
H13-U15
Power:
380V/50Hz,250V/50Hz,120V/38Hz
Size:
Customized Size
Air Velocity:
0.35-0.55m/s
Pre-filter:
With Or Not
Material:
Cold Rolled Steel/ Stainless Steel/ Galvalume
HEPA Filter:
H13-U15
Power:
380V/50Hz,250V/50Hz,120V/38Hz
Size:
Customized Size
Air Velocity:
0.35-0.55m/s
Pre-filter:
With Or Not
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom

Products Description
 
Laminar Air Flow FFU Clean Room FFU Fan Filter Unit  
 
Material of air chamber
Galvalume steel / Aluminum alloy / Stainless steel plate (304).
The introduction of fan filter unit
The fan filter unit is a self-powered terminal air supply device with filtering function, the fan sucks in air from the top and filters it through the HEPA filter in order to create clean air and evenly send out from the air outlet, it provides stable and strict air environment control for cleanrooms. The fan filter unit can be connected in modules to meet the needs of different enterprises and scientific research for different clean environments.
 

All sizes and styles can be customized
Model
YN-FFU-E01
YN-FFU-E02
YN-FFU-E03
YN-FFU-E04
Size (WxLxHmm)
575x575x344
575x1175x344
875x1175x374
1175x1175x374
Air chamber material
Galvalume / aluminum / stainless steel
Air Flow (m³/h)
800~900
1000~1100
1100~1200
1600~1700
Air velocity (m/s)
0.35~0.55
0.35~0.55
0.35~0.55
0.35~0.55
Total pressure (Pa)
175
185
195
255
Power (W)
85
95
115
235
Weight (kg)
27
37
40
42
Noise dB
(1m below the HEPA filter)
55~63
Vibration (mm/s)
0.2~0.7
Power supply
220V 1PH 50/60Hz (330V 3PH 50/60Hz 110V 1PH 50/60Hz)
Control mode
3 levels adjustable manually or group control by computer
Options
DOP inject port / DOP sample port / differential pressure drop test port /
differential pressure drop alarm device
HEPA filter
Size (WxHxDmm)
570x570x69
570x1170x69
870x1170x69
1170x1170x69
Efficiency
99.99% 0.3μm
Frame
High quality anodized aluminum
Initial
pressure drop
110Pa@0.45m/s±15%
Trait
PU foam endless gasket

 
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 0
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 1
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 2
 
 
YANING FFU Group Control System
According to different usage requirements, the FFU control method could be selectable from single control,
electric box small group control, touch screen small group control, computer group control etc.
 
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 3
 
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 4
 
 

Application
The fan filter unit is widely used in clean workshops of different cleanliness in many industries such as microelectronics / semiconductor, biopharmaceuticals, food processing, microbiological inspection and other places with strict air control requirements.
 
Company Information
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 5
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 6
YANING FFU Fan Filter Unit The HEPA Filter System Ceiling Of Cleanroom 7